To Proceed:
4. Press the RESET (READY) button.
5. Wait approximately 15 seconds for the FiveStar Alarm to
complete the fresh air adjustments.
During this time, the FIGURE 2-4 display appears.
After the fresh air adjustments are made, the FiveStar Alarm is
ready to complete span calibration.
The display appears (FIGURE 2-5):
The user can calibrate the gas sensors in the following order:
Combustible Gas
Oxygen
Toxic Gas #1
Toxic Gas #2
Toxic Gas #3
Figure 2-4.
Adjusting Zeroes
Figure 2-5.
Combustible Gas Calibration Display
Chapter 2, Calibration Technical Manual
2-4 FiveStar Alarm