Table 3-1. Troubleshooting Guidelines (continued)
ERROR
CODE
DESCRIPTION CORRECTIVE ACTION
1
Sensor board error Check/replace sensor board
2
EEPROM error
Reinitialize the instrument (follow procedure for
manual sensor configuration and answer yes
to query to reinitialize the EEPROM)
3
Pressure sensor error Replace the main board
4
unused
5
Combustible sensor error
Check/replace combustible sensor; if this does
not clear the error, replace the sensor board
(In an Australian approved instrument,
check the fuse on the main board if replacing
the sensor does not clear the error.)
6
Oxygen Sensor error Check/Replace the oxygen sensor
7
Combustible sensor zero error Check/replace the combustible sensor
8
Cannot write EEPROM Check/replace the main board
9
Battery type failure Replace battery pack
10
No sensors detected
Check to see if sensors and Zebra strips are
in place
11
Multiple sensors removed
from instrument
Check to see if sensors and Zebra strips are
in place
12
Combustible sensor missing Check combustible sensor and zebra strip
13
Oxygen sensor missing Check Oxygen sensor and zebra strip
14
Toxic 1 sensor missing Check Toxic 1 sensor and zebra strip
15
Toxic 2 sensor missing Check Toxic 2 sensor and zebra strip
16
Toxic 3 sensor missing Check Toxic 3 sensor and zebra strip
17
Multiple new sensors detected Run through sensor configuration
18
New combustible sensor installed Run through sensor configuration
19
New oxygen sensor installed Run through sensor configuration
20
New Toxic 1 sensor installed Run through sensor configuration
21
New Toxic 2 sensor installed Run through sensor configuration
22
New Toxic 3 sensor installed Run through sensor configuration
23
Multiple sensors installed in
illegal sites
Check sensor placement against TABLE 1-1
24
Improper sensor installed in
combustible site
Check sensor placement against TABLE 1-1
25
improper sensor installed in
oxygen site
Check sensor placement against TABLE 1-1
26
Improper sensor installed in
Toxic 1
Check sensor placement against TABLE 1-1
Chapter 3, Troubleshooting and Maintenance Technical Manual